Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RISER OVER 3' IN HEIGHT NOT SECURED TO CODE 2) FEEDERS FOUND IN HAZARDOUS CONDITION. DO NOT HAVE REQUIRED 8' CLEARANCE OVER ROOF TOPS 3) 6 APTS ON 1-100 AMP SERVICE/CAUSING OVER LOAD TO SYSTEM. UPGRADES REQUIRED 4) SYSTEM IS IN A HAZARDOUS CONDITION |