Permit: T09EL00405

Parcel: 117091770


Addresses:

1038 S HERBERT AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE WATER HEATER FLUE CONNECTION
2) EXTEND WH RELIEF LINE 6"-24" FROM GROUND
3) PROVIDE PROOF OF PERMTI REAR PORCH AND ADDED 220 & 110 CIRCUIT TO PORCH SECURE CONDUIT PROPERLY
4) REAR DOOR MISSING LIGHT FIXTURE SWITCHED
5) FURNACE INCOMPLETE
6) GFCI PROTECT BATH OUTLETS
7) 2 WIRE OUTLETS CHANGED WITH GROUND GFCI PROTECT HEAD OF CIRCUIT OR REPLACE WITH 2 WIRE ORIGINAL
8) SMOKE ALARM BEDROOMS AND HALLWAYS
9) PROVIDE CITY OF TUCSON SITE PLAN TO VERIFY ALL ADDITIONS ARE LEAGL