Permit: T09EL00362

Parcel: 128050670


Addresses:

5763 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/11/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/08/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAS TEST HAS LOST OVER 5 POUNDS-READS UNDER 10 AND IT STARTED AT OVER 15 PER PLUMBERS NOTE
2) FIND LEAK AND REDO TEST
05/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOTE: GAS PRESSURE TEST REQUIRED FOR GAS RECONNECT
2) PROVIDE UL LISTINF FOR FURNACE FLUE PIPE
3) WATER HEATER TPR MUST DRAIN DOWN INTO PAN, WHICH IS REQUIRED UNDER UNIT
3) PRESSURE RELIEF VALVE IS ALSO THEN REQUIRED ON THE MAIN WATER SUPPLY LINE
4) GAS LINES REQUIRE DRIP LEGS PRIOR TO UNITS
04/24/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) RECALL FOR ELECTRIC FINAL AFTER POWER IS RESTORED
04/16/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEPERATE DBL TAPED CIRCUIT WIRES IN SUB-PANEL
2) ISOLATE SUB-PANEL NEUTRALS AND GROUNDS
3) NO WIRING PRESENT, OR SPACE IN SUB-PANEL FOR WATER HEATER CIRCUIT
4) HAVE ALL 3 PRONG OUTLETS CHECKED FOR 2 WIRE SYSTEM
5) NOTE: GAS PRESSURE TEST REQUIRED FOR GAS RECONNECT
6) NOTE: ADD SERVICE UPGRADE TO PERMIT
02/25/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CORRECT ALL HAZARDOUS WIRING IN HOUSE BY A LICENSED ELECTRICIAN
2) INSTALL SMOKE DETECTORS IN BEDROOMS AND HALLWAY
3) INSTALL GFI'S IN KITCHEN COUNTER OUTLETS
4) NOTE: ELECTRICAL HAZARDS ARE EXTENSIVE-EXTERIOR, INTERIOR, MECHANICAL ROOM AND SHOP