Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/08/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS TEST HAS LOST OVER 5 POUNDS-READS UNDER 10 AND IT STARTED AT OVER 15 PER PLUMBERS NOTE 2) FIND LEAK AND REDO TEST |
|
| 05/05/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NOTE: GAS PRESSURE TEST REQUIRED FOR GAS RECONNECT 2) PROVIDE UL LISTINF FOR FURNACE FLUE PIPE 3) WATER HEATER TPR MUST DRAIN DOWN INTO PAN, WHICH IS REQUIRED UNDER UNIT 3) PRESSURE RELIEF VALVE IS ALSO THEN REQUIRED ON THE MAIN WATER SUPPLY LINE 4) GAS LINES REQUIRE DRIP LEGS PRIOR TO UNITS |
|
| 04/24/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RECALL FOR ELECTRIC FINAL AFTER POWER IS RESTORED |
|
| 04/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEPERATE DBL TAPED CIRCUIT WIRES IN SUB-PANEL 2) ISOLATE SUB-PANEL NEUTRALS AND GROUNDS 3) NO WIRING PRESENT, OR SPACE IN SUB-PANEL FOR WATER HEATER CIRCUIT 4) HAVE ALL 3 PRONG OUTLETS CHECKED FOR 2 WIRE SYSTEM 5) NOTE: GAS PRESSURE TEST REQUIRED FOR GAS RECONNECT 6) NOTE: ADD SERVICE UPGRADE TO PERMIT |
|
| 02/25/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CORRECT ALL HAZARDOUS WIRING IN HOUSE BY A LICENSED ELECTRICIAN 2) INSTALL SMOKE DETECTORS IN BEDROOMS AND HALLWAY 3) INSTALL GFI'S IN KITCHEN COUNTER OUTLETS 4) NOTE: ELECTRICAL HAZARDS ARE EXTENSIVE-EXTERIOR, INTERIOR, MECHANICAL ROOM AND SHOP |