Permit: T09EL00340

Parcel: 12002118A


Addresses:

4002 S 14TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
04/27/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
04/22/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEPERATE GROUND RODS MINIMUM 6' APART
04/21/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE SECONDARY GROUND ROD
2. PROVIDE GAS AND WATER BOND
3. RELOCATE SMOKIES 36" FROM REGISTERS AND HALLWAY
02/23/2009 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
CANCELED BY RICHARD
02/20/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*