Permit: T09EL00334

Parcel: 12007704A


Addresses:

536 W PALMDALE ST


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL00334

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
06/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/29/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE CODE COMPLIANCE NOTES
04/17/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DRAWING ON RECORD SHOWS GARAGE NOT GARAGE ENCLOSED TO ROOM
2. DRAWING DOES NOT SHOW FRONT PORCH
3. DRAWING SHOWS 4X10 HEADER PORCH @ PROPERTY LINE
4. DRAWING SHOWS 2X4 RAFTERS @ 16" O.C.
24" O.C INSTALLED
5. NO SITE PLAN ATTACHED PER PREVIOUS NOTES 11, 2, 4, 6, 7
6. PROVIDE WEATHERED FIXTURES EXTERIOR
7. NEW MECHANICAL DUCTS INSTALLED REQUIRE PERMIT
8. BLANK COVER SUB-PANEL MISSING BREAKER
04/16/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOUSE LOCKED UP
2) MESSAGE SAID IT WOULD BE LEFT OPEN
03/06/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST HOUSE NUMBERS VISIBLE FROM STREET
2) PROVIDE PROOF OF PORCH AND CARPORT ADDITION. PERMIT AT EAST PROPERTY LINE. VERIFY PERMIT CARPORT ENCLOSURE
3) WATER HEATER B-VENT MISSING CAP. PRESSURE RELIEF LINE MUST BE 3/4" COPPER OR CVPC
4) EXTERIOR DOORS REQUIRES SWITCHED LIGHTS
5) BARS ON BEDROM WINDOWS MUST OPERATE-WORK WITHOUT USE OF SEPERATE TOOLS
6) LABEL CIRCUITS SUB PANEL
7) 2-WIRE AND 2-WIRE WITH GROUND OUTLETS MIXED THROUGHOUT
8) HEAT REQUIRED ALL HABITABLE ROOMS
9) HAZARDOUS ELECTRICAL CEILING FANS
10) MISSING COVER PLATES
11) PROVIDE SITE PLAN OF RECORD TO VERIFY ALL ADDITIONS
02/20/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CAP OFF GAS LINE NOT BEING USED BY BACK WATER HEATER
2. VENT WATER HEATER PROPERLY
3. TPV VALVE NEEDED TO CODE FOR WATER HEATER
4. EXTERIOR BOX NEEDED FOR OUTLET BY WATER HEATER
5. SMOKE DETECTORS NEEDED IN BEDROOMS AND
ADJACENT HALLS
6. SWITCH PLATE COVERS