Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
03/04/2009 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
03/02/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH PREVIOUS NOTE #1
02/25/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND WIRE MUST BE CONTINOUS FROM GROUND ROD TO GROUND ROD
2) PROVIDE BRACE RISER OVER 36" ABOVE ROOF LINE
3) SECURE BARE WIRE #4 TO BLDG
02/19/2009 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UPGRADE NOT 200 AMP, 60 AMP TO 100 AMP
2) SECURE RISER TO BLDG
3) PROVIDE GAS AND WATER BOND
4) PROVIDE SECONDARY GROUND ROD 6' APART
5) PROVIDE U.L. LISTED RISER AND BRACE