Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/04/2009 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 03/02/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLY WITH PREVIOUS NOTE #1 |
|
| 02/25/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND WIRE MUST BE CONTINOUS FROM GROUND ROD TO GROUND ROD 2) PROVIDE BRACE RISER OVER 36" ABOVE ROOF LINE 3) SECURE BARE WIRE #4 TO BLDG |
|
| 02/19/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UPGRADE NOT 200 AMP, 60 AMP TO 100 AMP 2) SECURE RISER TO BLDG 3) PROVIDE GAS AND WATER BOND 4) PROVIDE SECONDARY GROUND ROD 6' APART 5) PROVIDE U.L. LISTED RISER AND BRACE |