Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/12/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST HOUSE NUMBERS VISIBLE FROM STREET 2) OMITTED ADDED ROMEX AT PANEL 3) LABEL CIRCUITS IN PANEL 4) HAZARDOUS WIRING REAR LAUNDRY ROOM 5) HAZARDOUS FITTINGS CONDUIT TO ROOF TOP 6) SECURE WATER HEATER B-VENT PROPERLY 7) EXTEND PRESSURE RELIEF LINE WATER HEATER 6"-24" FROM GROUND 8) SECURE WATER HEATER ENCLOSURE TO BLDG 9) PROVIDE PROOF LAUNDRY ADDTION PERMIT OR REMOVE 10) SMOKE ALARMS ALL BEDROOMS AND HALLWAYS 11) PANEL NOT GROUNDED DUE TO VANDALISM |