Permit: T09EL00173

Parcel: 12216234A


Addresses:

1779 N ALVERNON WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/27/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
PROVIDE CLEARANCE TO TEP FOR
NEW SERVICE WIRES FROM POWER POLE TO BUILDING
03/24/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE APPROVED SEALS FOR DEADFRONT COVER - NOT TAPE
2. LABEL CIRCUIT DIRECTORY 408.4 - LEGIBLE AND DISTINGUISHABLE LABEL PANEL COVER
3. PROTECT CONDUCTORS FROM SHARP METAL EDGES ENTERING PANEL
4. REMOVE COMBUSTIBLES FROM PANEL
5. USE LISTED MAST BRACE KIT
6. NEED REJECTION PINS
7. PROPERLY INSTALL GROUNDING ELECTRODE CONDUCTOR TO CLAMP - NOT UNDER