Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* PROVIDE CLEARANCE TO TEP FOR NEW SERVICE WIRES FROM POWER POLE TO BUILDING |
|
| 03/24/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE APPROVED SEALS FOR DEADFRONT COVER - NOT TAPE 2. LABEL CIRCUIT DIRECTORY 408.4 - LEGIBLE AND DISTINGUISHABLE LABEL PANEL COVER 3. PROTECT CONDUCTORS FROM SHARP METAL EDGES ENTERING PANEL 4. REMOVE COMBUSTIBLES FROM PANEL 5. USE LISTED MAST BRACE KIT 6. NEED REJECTION PINS 7. PROPERLY INSTALL GROUNDING ELECTRODE CONDUCTOR TO CLAMP - NOT UNDER |