Permit: T09EL00171

Parcel: 116123060

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
02/04/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
02/03/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED TO COVER ALL OPENING IN DEAD FACE COVER SERVICE PANEL
2. WILL NEED 2 GROUND RODS
3. ITEM #4 NOT MET #6 ALSO
01/30/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING FACE COVER ON SERVICE PANEL
2) GROUND WIRE HAS BEEN CUT-WILL NEED 2 GROUND RODS 6' APART WITH CONTINOUS GROUND WIRE
3) WILL NEED TO EXTEND TPR LINE ON WATER HEATER TO OUTSIDE OF BLDG
4) WATER HEATER NEEDS A SEDIMENT TRAP
5) RECEPTACLE AT LAUNDRY NEEDS TO BE GFI BECAUSE OF LAUNDRY TUB
6) NEED SMOKIES IN BEDROOM AND HALLWAY
7) KITCHEN SINK MUST BE IN PLACE AND WORKING
8) WILL NEED TO SUPPLY LADDER TO ACCESS ROOF
9) ALL WALL PLATE COVER MUST BE ON RECEPTACLES
10) WHAT TYPE OF HEATING IS BEING USED IN THIS DWELLING ?