Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE PROOF OF PERMIT FOR PORCH ADDITION @ FRONT 2. PROVIDE PROOF OF PERMIT FOR REAR PORCH ADDITION 3. PROVIDE PROOF OF PERMIT FOR ALL ADDITIONS ATTACHED TO MAIN HOUSE 4. COMPLY WITH NOTES 1-10 FROM PREVIOUS INSP. 5. MISSING COVER PLATES THROUGHOUT 6. PROVIDE SMOKE DETECTORS HALLWAY & BEDROOMS 7. GFCI PROTECT KITCHEN COUNTER OUTLETS 8. a. ADDITIONS IN QUESTION CLOSETS WEST END b. ALL PORCHES c. ROOMS TO EAST END |
|
| 02/03/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SERVICE PANEL SUPPORT FOR WEATHERHEAD BROKEN 2. IMPROPER WIRING OF BOTH RECEPTS AT REAR WALL CONDUIT, WIRES, BOXES 3. TWO 30 AMP. BREAKERS NOT TIED TOGETHER ONE 30 AMP, ONE 20 AMP GOING TO DRYER 4. 1/2 OF 2 POLE 30 FEEDING A 120V RECEPT (REAR PORCH) 5. BACK DOOR LIGHT FIXTURE WIRED IMPROPERLY 6. PROBLEMS AT WATER HEATER ROOM 7. LABEL ALL CIRCUITS 8. ROOF UNIT MISSING AC OR COOLER? WIRING CUT 9. COMBINATION NOT CORRECT FOR ENTRY 10. YOU NEED TO SUPPLY PROOF FOR PERMITTING OF ADDITIONS - CARPORT, ADD/ON EAST SIDE OR WAIT FOR ME TO OBTAIN CHECKED WITH JoANN ABOUT ADDITIONS VALID PERMITS FOR ADDITION OF PORCH, UTILITY ROOM, GAS LINE 1997-1998 |