Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/17/2009 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 07/23/2009 | ELECTRIC - RECONNECT | Partial Approval | ||
| 01/27/2009 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED GFI PROTECTED RECEPTACLES ON KITCHEN COUNTER SPACE AND BATHROOM 2) ALL BEDROOMS MUST HAVE SMOKE ALARMS 3) MECHANICAL ROOM NEEDS TO BE BROUGHT UP TO CODE, THE CEILING MUST BE FIRE SEALED 4) SUB PANEL BOX IN MECHANICAL ROOM NEEDS A BREAKER OR PLUG FOR EMPTY SPACE 5) WATER HEATER GAS LINE NEEDS SEDIMENT TRAP AND SO DOES GAS FURNACE 6) NEED TO SHOW PERMITS FOR WORK DONE AT CARPORT 7) NEED TO EXTEND GAS VENT DUCT 3' ABOVE COOLER WHEN LESS THAN 10' AWAY 8) WILL NEED LADDER TO ACCESS ROOF-TO INSPECT EMT LINE TO ROOF POWER |