Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/22/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAIN DISCONNECT REQUIRED PER 2006 IRC E3501.7 2) UNABLE TO LOCATE GROUNDRODS 3) APPROVED WATER PROOF NUT OR MYERS HUB REQUIRED WHEN ENTERING PANEL ABOVE BOTTOM OF BUSS BAR 4) LABEL ALL BREAKERS. LIGHTS AND PLUGS NOT ACCEPTABLE PER E3606.2 |