| 01/20/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/16/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SECURELY ATTACH GROUNDING ELECTRODE CONDUCTOR TO STRUCTURES 2. CONDUCTORS ACROSS PUBLIC STREETS TO BE 18' - 230.24(B)(4) 3. LABEL BREAKERS |