Permit: T09EL00069

Parcel: 128040420


Addresses:

5854 E 15TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
01/21/2009 ELECTRIC - SERVICE RELOCATION Approved IVRS - Inspection :*
01/20/2009 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND RODS MUST BE 6' APART MINIMUM
2) BOND WATER/GAS AT H20 HEATER
3) MOVE GROUND #4 TO PANEL JACKET
4) ISOLATE NEUTRAL BAR FROM JACKET