Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/21/2009 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 01/20/2009 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND RODS MUST BE 6' APART MINIMUM 2) BOND WATER/GAS AT H20 HEATER 3) MOVE GROUND #4 TO PANEL JACKET 4) ISOLATE NEUTRAL BAR FROM JACKET |