Permit: T09EL00015

Parcel: 137050920


Addresses:

5010 S 11TH AV #02


Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Permit Number - T09EL00015

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Denied

Date Description Inspector Results Comments
12/21/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WORKING ON PLATFORM AT SERVICE
2) 220V BREAKERS TO SPAN 2 PHASES AND USE MANUFACTURES HANDLE TIES
3) MAIN BACK FED BREAKER TO HAVE MANUFACTURES HOLDOWN
4) CONDUIT FITTINGS TO BE FOR WET LOCATION
5) INSTALL MAIN BONDING JUMPER
6) PVC LB-NO GLUE OR ADHESION TIGHTEN CONDUIT FITTINGS ALSO
7) FINISH ITEMS 1,2,3,5 & 7 OF PREVIOUS INSPECTION
08/07/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CANNOT ACCESS PANEL-BOTTOM OF PANEL AT 6'-6.5"
2) NEED 2ND GROUND ROD, GAS AND WATER BOND
3) USE APPROVED HARDWARE AND SEPERATE FROM COMBUSTIBLES FOR DEVICES
4) KITCHEN RECEPTACLES TO BE GFCI PROTECTED
5) PROVIDE DISCONNECTING MEANS FOR ROOM A/C UNITS
6) POST UNIT NUMBERS ON BLDG AND LABE SERVICE EQUIPMENT
7) PLEASE VERIFY PERMIT WHEN UNIT WAS RE-WIRED NM CABLE DATE STAMPED 6/26/08 ALSO FOR SERVICE EQUIPMENT