Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/11/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. LOAD CONDUCTOR NOT ALLOWED OUT TOP END WALL PER MANUFACTURER 2. BOND RISER 3. NEED ANTIOXIDE COMPOUND WITH ALUMINUM CONDUCTORS |
|
| 01/06/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. CLEAN INTERIOR OF MAIN PANEL OF FOREIGN SUBSTANCES AND CHECK CONDITION OF CONDUCTORS 2. USE APPROVED BOX FOR SPLICES AND LEAVE EXPOSED 3. GROUND JUNCTION BOX 4. BOX OVERFILLED |