Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/21/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RECALL FOR INSPECTION AFTER POWER IS ON |
|
| 01/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 2, 5 & 7 FROM PREVIOUS INSPECTION NEED TO BE COMPLETE 2) SMOKE DETECTORS MUST BE AT LEAST 36" AWAY FROM AIR DUCT AND AT LEAST 12" FROM CEILING LINE MAX. FOR PROPER LOCATION 3) OPE SPACE AT BREAKER PANEL, NEEDS TO BE PLUGGED 4) NEED TO VERIFY WORK DONE TO SHEDS BEHIND BLDG |
|
| 01/07/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BATHROOM RECEPTACLE TO BE GFCI PROTECTED 2. SMOKE DETECTORS TO BE AS PER MANUFACTURES INSTRUCTIONS 3. PROTECT BULBS IN CLOSETS 4. MISSING COVER PLATES 5. MISSING MAIN BREAKER 6. NEED WORKING CLEARANCES 7. PLEASE VERIFY PERMITS FOR NEW WORK INSTALLED THIS IS A RESIDENTIAL UNIT *UNIT IS OCCUPIED |