Addresses:

110 S CHURCH AV


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T09DV05349

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2009 INSP - INITIAL CODE ENFORCMENT Approved THE MEN'S LOCKER ROOM

THE INTERIOR OVERHEAD LIGHT FIXTURE IN THE SAUNA ROOM IS NOT PROPERLY SECURED AND DOES NOT HAVE APPROVED TYPE GLOB.

THE INTERIOR OVERHEAD LIGHT FIXTURE IN THE STEAM ROOM IS NOT PROPERLY SECURED AND DOES NOT HAVE APPROVED TYPE GLOB.

MISSING AND LOOSE COVER PLATES.

LIGHT BAR HAS ADAPTERS AND PLUGS IN THE BULB SOCKETS.

SERVICE ROOM HAS JUNCTION BOX NOT PROPERLY SECURED TO THE WALL.

ELECTRICAL EQUIPMENT IS BEING OBSTRUCTED WITHIN 30 INCHES IN WIDTH AND 36 INCHES IN DEPTH IN THE WASHER AND DRYER ROOM.

EXIT SIGN NOT PROPERLY MOUNTED

EXHAUST FAN IN BATHROOM NOT CONNECTED AND MISSING COVER THE UNIT IS UNSANITARY.
INTERIOR WALL SURFACE HAS DAMAGE AT THE AREA WHERE THE WALL MEETS THE FLOOR.

WALL SIDING IN URINAL AREA HAS DETACHED FROM THE WALL.

BASEBOARD HAS DETACHED FROM THE WALL.

WALL SURFACE ABOVE THE STEAM ROOM DOOR HAS SHOWS EVIDENCE OF MOISTURE DAMAGE.

AIR RETURN VENTS IN THE LOCKER ROOM ARE CLOGGED WITH DEBRIS
STAIRWAY WALKING SURFACE HAS VINYL NOSING THAT HAS DETACHED AND IS UNSERVICEABLE.