Case: T09DV05068

Parcel: 119041270


Addresses:

332 W AJO WY


Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Case Number - T09DV05068

Inspection Description - INSP - INITIAL CODE ENFORCMENT

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2009 INSP - INITIAL CODE ENFORCMENT Approved RESEARCH COMPLETED,

BUILDING IS BEING OCCUPIED WITHOUT A CERTIFICATE OF OCCUPANCY
BUSINESS BATTERY OUTLET
OPEN TO THE PUBLIC
NO APPROVED SITE PLAN FOR THE USE OF LAND.

PROPERTY IS BEING USE TO STORE OVER 100 PALLETS OF LEAD ACID BATTERIES ( OUTDOOR STORAGE )
ZONE IS C-2" COMMERCIAL ZONE
NEW ADDED CIRCUITS INSTALLED IN THE INTERIOR AND EXTERIOR OF THE BUILDING. THE INTERIOR CIRCUIT IS SUPPLYING POWER TO A SERIES OF JUNCTION BOXES. THE RACEWAY RUNS FROM THE PANEL BOARD IN CONDUIT AND RUNS ACROSS THE CEILING OF THE GARAGE TO A SERIES OF FOUR JUNCTION BOXES ATTACHED THE INTERIOR OF THE BUILDING.

THE EXTERIOR CIRCUIT IS SUPPLYING POWER TO A JUNCTION BOX UNDERNEATH THE CARPORT OF THE BUILDING. THE RACEWAY IS ARMORED CABLE THAT RUNS ON TOP OF THE METAL SHEATHING OF THE CARPORT TO THE JUNCTION BOX ATTACHED TO THE POLE OF THE CARPORT.

ACCESS TO THE SERVICE EQUIPMENT MAIN DISCONNECT LOCATED REAR OF THE BUILDING IS BEING BLOCKED BY PALLETS OF BATTERIES

INTERIOR PANEL BOARD DOES NOT HAVE APPROPRIATE PANEL SCHEDULED.
09/04/2009 INSP - INITIAL CODE ENFORCMENT Approved ON SITE INSPECTION OF THE BATTERY OUTLET BUSINESS
THE BUILDING IS BEING OCCUPIED WITHOUT A CERTIFICATE OF OCCUPANCY. THE BUSINESS IS IN C-2" COMMERCIAL ZONE.

RESEARCH RECORDS AT DSD AND FOUND NO APPROVED SITE PLAN
FOR THE CURRENT BATTERY OUTLET BUSINESS

NEW ADDED CIRCUITS INSTALLED IN THE INTERIOR AND EXTERIOR OF THE BUILDING. THE INTERIOR CIRCUIT IS SUPPLYING POWER TO A SERIES OF JUNCTION BOXES. THE EXTERIOR CIRCUIT IS SUPPLYING POWER TO A JUNCTION BOX UNDERNEATH THE CARPORT OF THE BUILDING.

THE MAIN DISCONNECT IS BEING BLOCKED WITH PALLETS OF BATTERIES NO ACCESS.

INTERIOR PANEL BOARD DOES NOT HAVE APPROPRIATE PANEL SCHEDULED.

AT REAR OF THE BUSINESS PROPERTY THERE IS A DWELLING, THERE IS NO WALL SEPARATION BETWEEN THE COMMERCIAL ZONE AND THE RESIDENTIAL USE. THERE IS A CHAIN LINK FENCE AT THE LOT LINE BETWEEN PROPERTIES.

THERE ARE OVER ONE HUNDRED PALLETS OF BATTERIES BEING STORED AT THE REAR OF THE BUILDING BETWEEN THE BUILDING FACE AND THE LOT LINE.
08/28/2009 INSP - INITIAL CODE ENFORCMENT Approved PEDDLER CITED FOR OPERATING WITH EXPIRED LICENSE, NOTICE WAS GIVEN AND SHUT THE BUSINESS DOWN.
WILL RESEARCH PROPERTY AT DSD FOR SITE PLAN APPROVALS