Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T09DV00255

Parcel: 11941176B


Addresses:

1725 W AJO WY

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
01/22/2009 INSP - INITIAL CODE ENFORCMENT Approved 1-22-2009 5:19 AM
1725 W AJO WAY
FIRE CALL TO BUSINESS LOS BETOS RESTAURANT
FIRE DAMAGE TO COMMERCIAL GRADE HOOD IN THE KITCHEN
THE METAL TO THE HOOD HAS DISCOLORED AND SEPARATED. THE HOOD IS DILAPIDATED. THE FIRE SUPPRESSION SYSTEM (CHEMICAL TYPE ) DID NOT ENGAGE DUE TO LACK OF MAINTENANCE IN THE AREA OF THE FUSIBLE LINKS WHICH HAVE A CABLE SYSTEM WITH TENSION TO THE CHEMICAL CONTAINER. THE CONTAINER GAUGE DID INDICATE A FULL CHARGED STATUS. THE INSPECTION CARD ON THE OVERRIDE MANUAL SYSTEM DID HAVE AN INSPECTION DATE OF DECEMBER 2008.

HEALTH DEPT WAS ON SITE

THE GAS METER WAS PINNED OFF BY SOUTHWEST GAS

CODE ENFORCEMENT ACTION TAKEN
ISSUED VIOLATION NOTICE 0 DAYS
NO USE OF THE GAS COOKING SYSTEMS OR AREA IN THE KITCHEN.

PERMITS REQUIRED FOR ALL REPAIR OR REPLACEMENT OF HOOD AND ALL RELATED SYSTEMS. GAS TURN ON.

REPAIR ALL INSPECTION HOLES IN THE INTERIOR AND ROOF