Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T09CM03431
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2010 | PLUMBING - INTERMEDIATE | Approved | ||
04/01/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*IVRS - Inspection :* 1) ISOLATE ABS FROM METAL STUDS 2) ABS TO BE SUPPORTED EVERY FOUR FEET |
|
03/08/2010 | PLUMBING - INTERMEDIATE | Denied | 1) REVISE PLAN FOR NEW (NOT EXISTING) 1" COLD WATER TO STREET. 2) SHOW ALL REQUIRED BACKFLOW DEVICES. 3) PLEASE PROVIDE GAS ISOMETRIC TO VERIFY SIZING & SHOW ACTUAL INSTALLED CONDITIONS. 4) GAS PIPING TO "EXISTING" 50,000 BTU FURNACE DOES NOT ACCOUNT FOR THE FACT THAT THIS IS A NEW USE. IT IS UNLIKELY THAT A 50K BTU FURNACE WILL HEAT THIS SPACE PROPERLY AS SHOWN. 5) REVISE PLUMBING PLANS TO SHOW ENTIRE SYSTEM (INCLUDING EXISTING), AND INDICATE WHERE REPAIRS HAVE BEEN MADE. 6) BASEMENT CONDITIONS NOT NOTED ON PLAN. 7) SCULLERY AREA OK TO COVER. |
|
03/03/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |