Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T09CM03431
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2010 | FRAMING | Approved | IVRS - Inspection :* 1) BASEMENT, GROUND FLOOR AND MEZZANENE OK |
|
03/08/2010 | FRAMING | Denied | 1) AREA CALCULATIONS ARE INCORRECT. MUST SHOW ENTIRE AREA OF BUILDING & WHETHER OR NOT THIS IS SEPARATED USE. 2) STORE-FRONT HAS BEEN REMOVED. PLEASE PROVIDE DETAILS ALONG WITH C.O.T. HISTORIC AND DESIGN REVIEW BOARD APPROVALS FOR REBUILD. 3) SHOW BASEMENT AREA AND MEZZANINE AREAS ON PLANS AND INCLUDE IN AREA CALCULATIONS. 4) SCULLERY HAS BECOME PART & PARCEL OF BASEMENT. PLEASE HAVE FIRE DEPT. ADDRESS SPRINKLER REQUIREMENTS FOR THESE AREAS. 5) NOMENCLATURE "FIRE-TAPE" ON PLANS DOES NOT MEAN ANYTHING BY ITSELF. PLEASE SHOW ANY FIRESTOP SYSTEMS YOU WILL BE USING. 6) PLEASE SHOW WHAT WILL BE USED TO REPLACE THE DEMO'D FLOORING IN THE PATIO AND SCULLERY. 7) REQUIRE AREA SEPARATIONS HAVE NOT BEEN COMPLIED WITH FOR THE MEZZANINE STORAGE AREA. 8) MUST REPLACE BRICK IN THE NOTED 2 HOUR PROPERTY LINE WALL. 9) SHOW ALL EGRESS, CORRIDOR WIDTHS, DOOR SIZES, ETC. NEED CORRECT WIDTH TO EXISTING RESTROOM. 3) |
|
03/03/2010 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |