Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/09/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/19/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DUCT ON ROOF TO BE INSULATED MIN. R-8 2) CONDENSATE PIPE TO BE BLOCKED UP OFF ROOF MIN. 1.5" 3) CONDENSATE PIPE TO TERMINATE 6" ABOVE GRADE 4) CONDENSATE PIPE TO BE PAINTED 5) PROVIDE ROOF JACK ON ELECTRICAL CONDUIT 6) UNIT IS OVERFUSED 7) UNIT DATA PLATE NOT IDENTIFIED 8) DUCT ON ROOF SMASHED AND JOINTS ARE BROKEN OPEN |
|
| 01/08/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |