Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM03415
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2010 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/26/2010 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) LETTER FROM ENGINEERING FOR START COLLARS AND FLEX DUCT LENGTH IS OK 2) 1 GREASE DUCT OK FOR 1ST LAYER OF FIRE WRAP, 2ND DUCT IS LEAKING 3) PROVIDE A LETTER FROM ENGINEER IF ELIMINATING ANY FIRE WRAP |
|
03/22/2010 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE 125% CONICAL TAPS PER DETAILS NO DAE TAILS 2) INSTALL FLEX PER DETAILS (NOT TO EXCEED 4') 3) VERIFY SOUND INSULATION IN CURBS 4) PROVIDE 45 PERCENT ENTRY AT DUCT BRANCH ENTRY PER DETAIL (45 PERCENT TOWARDS AIR FLOW) |