Permit: T09CM03415

Parcel: 10511061R

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09CM03415

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/13/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
05/11/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) AT LAVATORIES: SEE DETAIL 204 ON SHEET P2.1
2) AT WATER HEATER: SEE DETAIL 209 ON SHEET P2.1
3) BACKFLOW PREVENTER AT ICE MACHINE MAY NOT BE ABOVE FIVE FEET
4) INDIRECT WAST PIPING EXCEEDING 5 FEET IN DEVELOPED LENGTH TO BE DIRECTLY TRAPPED-USE DRAINAGE FITTINGS
5) FILL HOT AND HOT RECIRC. PIPING TO BE INSULATED
6) ICE MAKER DRAIN MAY NOT COMBINE WITH ICE BIN DRAIN
7) BACTERIA REPORT, STERILIZATION, CERTS AND ANSUL VALVE SIGN