Permit: T09CM03414

Parcel: 12212026B


Addresses:

4443 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
04/01/2010 FIRE - FINAL Approved Approved
03/31/2010 FIRE - FINAL Partial Approval 1. Electrical blank required in panel 'A'.
2. Escutcheon needs to be sealed in rest room.
3. Annual sprinkler test required and 5 year check valve test required.
4. Missing 1 Fire Department Connection cover plate.
5. West middle door requires sign: 'THIS DOOR TO REMAIN OPEN WHEN BUILDING IS OCCUPIED'
6. Pottery room- sheet rock door which is not an exit.
7. Pottery room- remove sign on double door 'NOT AN EXIT. THIS DOOR IS BLOCKED'.
8. Repair hole above electrical panel in pottery room.