Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2010 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 03/29/2010 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TEST TO HOLD FOR 15 MINUTES WITH NO LOSS OF PRESSURE 2) PROVIDE APPROVED GAS SHUT OFF VALVES AT ALL APPLIANCES 3) PROVIDE 1" MINIMUM CLEARANCE FOR DBL WALL VENT AND COMBUSTIBLE 4) REATTACH HANGER ON 2" EXISTING 5) PROVIDE SUPPORT AT UH-2 FOR GAS PIPING |
|
| 03/15/2010 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) REQUIRE MINIMUM TEN POUND TEST ON GAS |