Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/08/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ABS REQUIRES SUPPORT AT CHANGE OF ELEVATION OR DIRECTION AND NOT EXCEEDING 4'-ADD TWO SUPPORTS 2) REMOVE EXCESS FLEX FROM SOLIDER JOINTS, SUPPORT WATER HEATER DRAINS 3) CAP OPEN DRAIN PIPES ABOVE CEILING AND AT RAMP |
|
| 03/04/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 01/26/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED TO REINSPECT SUPPORTS ON ABS AT ? AND VTR 2) DEMO OK 3) IN WALLS OK 4) WH ABOVE TOILET ROOM REQUIRES CODE CORRECTIONS 5) T & P, PAN, EXP TANK AND VAC RELIEF VALVE |