Permit: T09CM03408

Parcel: 13409018B


Addresses:

8578 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/24/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
2) TESTED DUCT SMOKE DETECTORS
3) AIR BALANCE OK
09/23/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AIR BALANCE REPORT
2) PROVIDE AUDIBLE AND VISIBLE ALARMS FOR DUCT SMOKE DETECTORS-NEED TO TEST
3) SUPPORT ELECTRIC CONDUITS TO CONDENSORS
4) PAINT EXPOSED PVC ON ROOF WITH LATEX PAINT
5) CAPTURE AND CONTAINMENT TEST FAILED