Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2010 | ELECTRIC - SERVICE UPGRADE | Partial Approval | 3518 E. 3RD ST-DENIED: 1) NEED BONDING BUSHING ON NIPPLE 2) NEED GROUND ELECTRODE CONDUCTOR UNDER PANEL STRAPED 3520 E. 3RD ST-DENIED: 1) NEED BOND BUSHING ON NIPPLE 2) NEED TO MOVE GAS METER OR PANL 3) NEED WATER BOND 4) NEED TO ANCHOR METER BASES 3524 E. 3RD ST-DENIED |
|
| 04/19/2010 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/19/2010 | ELECTRIC - SERVICE UPGRADE | Approved |