Permit: T09CM03389

Parcel: 12701005D

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/24/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
03/04/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE DUCT SMOKE DETECTORS
2) OK FOR CEILING TILES
03/03/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE BEADED COLLARS ON ALL SUPPLY DIFFUSERS
2) PROVIDE DUCT SMOKE DETECTORS AS PER PLANS
02/23/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPLY AND EXHAUST IN RESTROOMS OK TO SHEETROCK
02/19/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO COVER LINEAR DIFFUSERS IN SOFFIT AT SOUTH END OF BLDG