| 12/01/2010 | PLUMBING - FINAL | Approved | ||
| 04/08/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CARBONATOR NOT CONNECTED TO RPA, ALSO NEED REPORT FOR SVB |
|
| 04/07/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/25/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE WORK NOTED ON 3/24/10 INSPECTION HISTORY |
|
| 03/24/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE AN RPA FOR WATER SUPPLY TO CARONATOR 2) PROVIDE CLEARANCE TO SERVICE SVB (LOWER IT) 3) PROVIDE CERTS 4) CORRECT SLOPE OF DRAIN HOSE FROM ICE MAKER 5) PLAN SPECIFIES STERILIZATION OF WATER SYSTEM 6) PROVIDE A TRAP PRIMER FOR UNUSED FS P-7 7) TANK TYPE URINAL NOT SPECIFIED 8) PROVIDE DOCUMENTATION FOR CHANGES TO PLAN SPECS 9) PERM CAP ANY ABANDON VENT TERMINATIONS 10) RELOCATE ANY EXISTING VENT TERMINATIONS LOCATED WITHIN 10' OF NEW AIR INTAKES |