Permit: T09CM03389

Parcel: 12701005D

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09CM03389

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/01/2010 PLUMBING - FINAL Approved
04/08/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CARBONATOR NOT CONNECTED TO RPA, ALSO NEED REPORT FOR SVB
04/07/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
03/25/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) COMPLETE WORK NOTED ON 3/24/10 INSPECTION HISTORY
03/24/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE AN RPA FOR WATER SUPPLY TO CARONATOR
2) PROVIDE CLEARANCE TO SERVICE SVB (LOWER IT)
3) PROVIDE CERTS
4) CORRECT SLOPE OF DRAIN HOSE FROM ICE MAKER
5) PLAN SPECIFIES STERILIZATION OF WATER SYSTEM
6) PROVIDE A TRAP PRIMER FOR UNUSED FS P-7
7) TANK TYPE URINAL NOT SPECIFIED
8) PROVIDE DOCUMENTATION FOR CHANGES TO PLAN SPECS
9) PERM CAP ANY ABANDON VENT TERMINATIONS
10) RELOCATE ANY EXISTING VENT TERMINATIONS LOCATED WITHIN 10' OF NEW AIR INTAKES