Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
Permit Number - T09CM03370
Inspection Description - BUILDING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/08/2010 | BUILDING - PROGRESS | Approved | IVRS - Inspection :* | |
01/12/2010 | BUILDING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER HEATER VENT REQUIRES 6" CLEAR FROM COMBUSTIBLE FOR SINGLE WALL 1" FOR DBL WALL PROVIDE PTR LINE 6" MINIMUM 24" MAXIMUM FROM THE GROUND 2) 2 X 6'S STILL OVERSPAN 3) PLACE 4 X 8 MINIMUM BEAM AT MID SPAN 4) PROVIDE 16" X 16" FTG AT EACH POST 5) REPLACE BEAM, 4 X 4 WITH 4 X 6'S 6) INSTALL JOIST HANGERS AT EXISTING HOUSE OVERHANG 7) INSTALL CLOTHES WASHER DRAIN PER CODE 8) EXISTING BEDROOM ELECTRIC AND FRAMING APPROVED |
|
12/29/2009 | BUILDING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WINDOWS IN BEDROOMS SHALL BE 4'-4' MIN-NO PERMANENT WINDOW GUARDS 2) RELOCATE PORCH SUPPORTS TO 3' FROM PROPERTY LINE 3) 2 X 6 AT PORCH OVERSPAN 2 X 6 AT 24" ON CENTER, 12'-0" MAX SPAN 4) BREAKER COVER MISSING AT ELECTRIC SERVICE PANEL 5) HAVE LICENSED ELECTRICIAN CHECK ELECTRICAL IN 2 BEDROOMS AND VERIFY CODE COMPLIANCE IN WRITING IN COMPANY LETTER HEAD 6) B-VENT MISSING AT WATHER HEATER |