Permit: T09CM03370

Parcel: 13813116A


Addresses:

159 W MOSSMAN RD

Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Date Description Inspector Results Comments
04/08/2010 BUILDING - PROGRESS Approved IVRS - Inspection :*
01/12/2010 BUILDING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER HEATER VENT REQUIRES 6" CLEAR FROM COMBUSTIBLE FOR SINGLE WALL 1" FOR DBL WALL PROVIDE PTR LINE 6" MINIMUM 24" MAXIMUM FROM THE GROUND
2) 2 X 6'S STILL OVERSPAN
3) PLACE 4 X 8 MINIMUM BEAM AT MID SPAN
4) PROVIDE 16" X 16" FTG AT EACH POST
5) REPLACE BEAM, 4 X 4 WITH 4 X 6'S
6) INSTALL JOIST HANGERS AT EXISTING HOUSE OVERHANG
7) INSTALL CLOTHES WASHER DRAIN PER CODE
8) EXISTING BEDROOM ELECTRIC AND FRAMING APPROVED
12/29/2009 BUILDING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WINDOWS IN BEDROOMS SHALL BE 4'-4' MIN-NO PERMANENT WINDOW GUARDS
2) RELOCATE PORCH SUPPORTS TO 3' FROM PROPERTY LINE
3) 2 X 6 AT PORCH OVERSPAN 2 X 6 AT 24" ON CENTER, 12'-0" MAX SPAN
4) BREAKER COVER MISSING AT ELECTRIC SERVICE PANEL
5) HAVE LICENSED ELECTRICIAN CHECK ELECTRICAL IN 2 BEDROOMS AND VERIFY CODE COMPLIANCE IN WRITING IN COMPANY LETTER HEAD
6) B-VENT MISSING AT WATHER HEATER