Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/10/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK SWITCH BOARD ENTRANCES 2) TERMINATE CONDUCTOR BEFORE ENERGIZING EQUIPMENT |
|
| 09/07/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK RACEWAYS DOWN TO DISTRIBUTION PANEL 2) DISCUSSED 408.3 WITH CONTRACTOR |
|
| 08/23/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CONTRACTOR TO SLEEVE CONDUCTOR THRU ONE SECTION INTO 2ND SECTION TO ISOLATE PER 408.3 AS DISCUSSED |
|
| 08/20/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |