Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T09CM03355
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
01/27/2010 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*. 1) 50 AMP BREAKER TO LARGE-45 AMP IS MAX. USE A SQUARE D BREAKER 2) ID CIRCUIT BREAKER 3) PROVIDE A TRAP IN CONDENSATE DRAIN LINE AND PUT ELBOW & NIPPLE AT BOTTOM OF PIPE |