Permit Number - T09CM03355

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/08/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/27/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*.
1) 50 AMP BREAKER TO LARGE-45 AMP IS MAX. USE A SQUARE D BREAKER
2) ID CIRCUIT BREAKER
3) PROVIDE A TRAP IN CONDENSATE DRAIN LINE AND PUT ELBOW & NIPPLE AT BOTTOM OF PIPE