Inspection History Details
Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2012 | OUTDOOR LIGHTING FINAL | Approved | IVRS - Inspection :* | |
| 08/07/2012 | OUTDOOR LIGHTING FINAL | Partial Approval | 1) SIGN CIRCUITS TO BE PER 600.5 2) GROUNDING OF POLE TO BE AS DISCUSSED 3) SPLICES TO BE FOR WET LOCATION 4) GROUNDING AT SES 250.02 AND TIGHTEN BUSHINGS AND CONNECTIONS 5) PLEASE PROVIDE COPY OF SES GFI TEST REPORT |
|
| 02/24/2011 | OUTDOOR LIGHTING FINAL | Partial Approval | REOPENED FOR REVISION TO NORTH LOOP RD. LEERAY |