Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM03354
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/10/2012 | ELECTRIC - FINAL | Partial Approval | MEET WITH ENGINEER TO DISCUSS SIGNS AND 600.5 NEC IT WAS SUGGESTED TO SUBMIT APPEAL. | |
08/07/2012 | ELECTRIC - FINAL | Partial Approval | 1) SIGN CIRCUITS TO BE PER 600.5 2) GROUNDING OF POLE TO BE AS DISCUSSED 3) SPLICES TO BE FOR WET LOCATION 4) GROUNDING AT SES 250.02 AND TIGHTEN BUSHINGS AND CONNECTIONS 5) PLEASE PROVIDE COPY OF SES GFI TEST REPORT |