Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09CM03354

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T09CM03354

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2012 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
03/07/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 5 LIGHT POLE FOOTINGS NORTH SIDE
03/05/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
12/15/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) GROUND RING WITH 4 GROUND ROD #3/0 GROUND DISTRIBUTION
12/05/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) INSPECTIONS ON BOTH PERMITS, NOTE 1
2) SWITCH GEAR UNDERGROUND OK
04/07/2011 ELECTRIC - UNDERGROUND Partial Approval INSPECTION REOPENED FOR REVISION TO NORTH LOOP RD
01/13/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) DITCH NEXT TO PATIO BLDG 2-4" 140' OK
01/11/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 2-4" FOR POWER PATIO BLDG IS NEXT TO DITCH ON NORTH SIDE 130' OK
01/06/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 7 LIGHT POLES 1-1" IN AND OUT PARKING
2) 10+ LIGHTING OK
12/16/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) STUB UP 4-4" FOR POWER AND COMMUNICATIONS AT PATIO BLDG
12/07/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 100' OF 4-4" PVC GOING WEST OF CRAYCROFT TOWARDS BEVERLY OK
12/01/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 120' OF 2-4" PVC FROM CRAYCROFT TOWARDS BEVERLY OK COMMUNICATION AND POWER
11/10/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK STUB OUTS AT FOOTING FOR SIGN
2) OK U.G. FOR POLE LIGHTS 40' AT NORTH CORNER
11/03/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 1" PVC MEDIAN AREA EAST SIDE FOR POLE LIGHTS
10/20/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK U.G. 4" PVC NORTH SIDE OF TRAFFIC BRIDGE TO PEDESTAL BRIDGE
10/18/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 4-4" PVC HEADING NORTH FROM BRIDGE 80'
10/08/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) VEHICLE BRIDGE AREA-COMMUNICATIONS LINES (N & S RUN) OK TO COVER
10/01/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 10' 4" PVC AND 10' 1" PVC WEST OUT OF BRIDGE
09/24/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK PVC U.G. AT BRIDGE AND CRAYCROFT LTG AND DCUT THRU BRIDGE AT EAST OF BRIDGE ALL U.G.
09/21/2010 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
09/20/2010 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1) SCHEDULED BY ERROR
09/17/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
09/14/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
09/10/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PVC IN TRENCH ON CRAYCROFT OK
09/09/2010 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER CONTRACTOR
09/08/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 70' PVC IN TRENCH FROM GRANT AND CRAYCROFT NORTH
09/02/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 120' FROM SOUTH TO NORTH ON CRAYCROFT TRENCH OK
09/01/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 3-1" PVC FOR LIGHTING ON BRIDGE OK
2) COLVERT HAS 20' OF 4-6" PVC ON EACH SIDE OK 40' IN ALL
3) 110' OF 4-4" SOUTH TO NORTH ON CRAYCROFT ALL PVC OK
08/31/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) BRIDGE COLUMN LIGHT PVC 3/4" #4 GROUND COILED ON BOTTOM 3/4 AROUND TO LIGHT ON OTHER END
08/27/2010 ELECTRIC - UNDERGROUND Partial Approval 1) CANCELLED PER CONTRACTOR
08/26/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) SOUTH EAST CORNER OF PARKING LOT JUNCTION STUBS PHONE, POWER, COMMUNICATION, 1-1" WELL PEED, 50' MORE OF PVC 2-4" FOR POWER, 2-4" FOR COMMUNICATION IN TRENCH OK ALL IN PVC
08/25/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 4-4" COMMUNICATIONS, POWER 1-2" PUMP CONTROL IN DITCH 50' OK EASTSIDE OF PARKING LOT
2) SOUTH SIDE OF BLDG 4-4" POWER, COMMUNICATIONS IN DITCH 50' MORE OK
08/18/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 2-4" 60' PVC IN TRENCH IN CONCRETE FOR POWER
2) 2-4" 60' PVC ON TOP FOR COMMUNICATIONS
08/12/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 2-4" ON BOTTOM ENCASED IN RED CONCRETE FOR LOOP FEED FOR GENERATOR
2) 2-4" ON TOP OF COMMUNICATION
07/07/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 2-4" PVC IN TRENCH IN CONCRETE DOCK BANK COMMUNICATION ON TOP-2-4" PVC ALL OK
06/17/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
2-4" PVC 110" LONG TRENCH OK EAST PARKING LOT
06/15/2010 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
06/11/2010 ELECTRIC - UNDERGROUND Partial Approval 1) ACCESS DRIVEWAY OF SOUTHEAST PARKING LOT OK
06/02/2010 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 1" PVC IN AND OUT FOR PARKING LOT LIGHTING 8 POLES #4 SOLID FOR GROUNDING ELECTRODE OK