Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/23/2011 | MECHANICAL - FINAL | Partial Approval | A/C FANS & EXHAUST FAN MUST RUN CONTINUOUSLY DURING OCCUPIED HOURS. PROVIDE AIR BALANCE REPORT. PROVIDE CO2 SENSORS AS PER PLANS. TESTED DUCT SMOKE DETECTORS. |