Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2010 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* 1) TOP OUT, COMPLIANT STRUCTUAL CONCEPT |
|
| 06/28/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) EXTERIOR WALLS TO 19' 4" VARIES TO 20' 2) SPECIAL INSPECTED |
|
| 06/24/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) NORTH WALL TO 16' OK SPECIAL INSPECTED |
|
| 06/22/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) 4TH LIFT TO 16' EAST,WEST AND SOUTH WALL 2) WEST WALL TO 12' |
|
| 06/21/2010 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
| 06/17/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
| 06/15/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* | |
| 06/11/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) EXTERIOR MASONRY WALL STEEL REINFORCEMENT FROM TOP OF STEM WALL TO 4' AFFE OK TO GROUT-SPECIAL INSPECTION BY STRUCTURAL CONCEPTS/NELSON |
|
| 06/10/2010 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* 1) PER GENERAL NOTES 48 BAR MINIMUM LAP 30" FOR #5 YOU HAVE 24" PROVIDE ENGINEER STAMPED RFI |
|
| 05/24/2010 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) CONTINOUS STEM WALL AT 16"-OK TO GROUT PROGRESS AREAS |