Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T09CM03317
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/05/2011 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* | |
09/08/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* | |
09/06/2011 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* | |
03/02/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) FROM MANHOLE #1 TO #2 AIR TEST OK 2) FROM MANHOLE #2 TO #3 AIR TEST OK 3) FROM MANHOLE #3 TO BLDG AIR TEST OK 4) FROM PUBLIC TO MANHOLE #3 AIR TEST OK 5) MIRROR AND MADRIL BY CHRIS |
|
02/28/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | 1. BASES SET FOR MANHOLES 1, 2, 3, AND RINGS STACKED. | |
02/25/2011 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER JACK |
|
02/24/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) CONTINUATION OF 8" TO MANHOLE #1, 6" FROM MANHOLE #1 TO 10' FROM BLDG, BEDDING, LAYING TRACER AND SHADING 2) TEST AT LATER DATE |
|
02/22/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) 8" SDR INSTALLED AND SHADED THRU MAN HOLES 2 & 3-OK SUBJECT TO TESTING AND VERIFICATION OF GRADE 2) INSTALL WATER STOPS PRIOR TO POURING BASES |
|
02/17/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* | |
02/15/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) FROM PUBLIC 8" SDR CONTINUES APP. 154' NORTH BEDDING, ?, TRACER SHADING CONTINUE BACKFILL TEST LATER |
|
02/14/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 1) 8" SDR CONTINUES NORTH APP. 100' FROM PUBLIC MAN HOLE. OK TO START BACKFILLING BEDDING, LAYING, TRACER AND SHADING |
|
02/11/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | 1. 8' SDR 35 CONTINUES APPROXIMATELY 80 FEET FROM PUBLIC MANHOLE NORTH, BEDDING, LAYING, TRACING, SHADING. | |
02/10/2011 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :*PUBLIS MANHOLE CORED WITH 8" SDR 14' TO NORTH BEDDING LAYING TRACER SHADEING OK TO PROCEED, TESTING AT LATER DATE. |