Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/29/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE FIXTURES TO INSP GROUNDING |
|
| 04/27/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) GATE LOCKED, NO MSG. RECALL INSPECTION |
|
| 04/15/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO STRAP 1/2 EMT ON ROOF 3" FROM BOX MISSING 2 2) NEED TO BOND LIGHTS AND ALL J-BOXES 3) NEED TO TIGHTEN CONNECTOR |