Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM03304

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/22/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
03/28/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) EXHAUST STACK ? PER INSTALL INSTRUCTIONS
2) PAN WASHER EXHAUST/FLUE OK
3) PROVIDE HEAT SENSOR INTER LOCK AT ALL TYPE 1 HOODS
4) GAS PRESSURE TEST OK LEFT GAS TAG
03/24/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) BAKERY AREA EXHAUST DUCT AT OVENS PRESSING AGAINST SPRINKLER PIPING
2) ALL OTHER CEILING GRILLS OK TO COVER
3) BAKERS RACK WASHER FLUE PIPE NOT PROPERLY SUPPORTED
03/14/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE LETTER FROM CONTROLS CONTRACTOR ON DUCT SMOKE DETECTOR OPERATION
03/11/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/10/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/09/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FLEX DUCT AT WALK-IN'S OK TO COVER
02/24/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PHARMACY/OFFICES ABOVE CEILING OK TO COVER DUCT
02/23/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE SEISMIC RESTRAINTS ON REGISTERS
2) INSULATE SQUARE TO ?
3) GRID WIRE BLOCKING ACCESS TO CONTROL BOX ON VAV
4) RETURN CANS MUST BE SCREWED TO REGISTERS
5) PROVIDE MINIMUM 2" BEADED COLLARS AT ALL FLEX DUCT CONNECTIONS
02/22/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT ABOVE CEILING OK
2) DUCT ABOVE MEAT PREP OK
3) ALL REFRIDGERATION HARD DUCT INSTALLED OK
02/11/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ALL RESTROOM EXHAUST OK TO COVER, EXCEPT TIRE CENTER
02/08/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/07/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. AN-2 CHICKEN PREP AREA ROUGH DUCT OK TO INSULATE.
2. ROUND DUCT AT PHARMACY OK TO INSULATE PROVIDE BRANCH TAPS PER PLANS.
3. ROUND DUCT AT OFFICE AREA OK TO INSULATE.
4. ROUND DUCT AT OPTICAL OK TO INSULATE.
02/03/2011 MECHANICAL - ABOVE CEILING Cancelled IVRS - RI canceled
01/25/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT ABOVE MEAT PREP OK TO COVER
01/21/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE CONICAL TAPS PER PLANS/DETAILS
2) PROVIDE 45 DEGREE CONVERGING BRANCH TAPS ON RECTANGULAR DUCT PER PLANS/DETAILS
3) PROVIDE RADIUS THROATS ON RECTANGULAR ELBOWS PER PLANS/SPECS
4) PROVIDE WRITTEN APPROVAL FROM ENGINEER ON ALL CHANGES TO PLANS