Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM03304
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
03/28/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) EXHAUST STACK ? PER INSTALL INSTRUCTIONS 2) PAN WASHER EXHAUST/FLUE OK 3) PROVIDE HEAT SENSOR INTER LOCK AT ALL TYPE 1 HOODS 4) GAS PRESSURE TEST OK LEFT GAS TAG |
|
03/24/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BAKERY AREA EXHAUST DUCT AT OVENS PRESSING AGAINST SPRINKLER PIPING 2) ALL OTHER CEILING GRILLS OK TO COVER 3) BAKERS RACK WASHER FLUE PIPE NOT PROPERLY SUPPORTED |
|
03/14/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE LETTER FROM CONTROLS CONTRACTOR ON DUCT SMOKE DETECTOR OPERATION |
|
03/11/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/10/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/09/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FLEX DUCT AT WALK-IN'S OK TO COVER |
|
02/24/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PHARMACY/OFFICES ABOVE CEILING OK TO COVER DUCT |
|
02/23/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE SEISMIC RESTRAINTS ON REGISTERS 2) INSULATE SQUARE TO ? 3) GRID WIRE BLOCKING ACCESS TO CONTROL BOX ON VAV 4) RETURN CANS MUST BE SCREWED TO REGISTERS 5) PROVIDE MINIMUM 2" BEADED COLLARS AT ALL FLEX DUCT CONNECTIONS |
|
02/22/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) DUCT ABOVE CEILING OK 2) DUCT ABOVE MEAT PREP OK 3) ALL REFRIDGERATION HARD DUCT INSTALLED OK |
|
02/11/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ALL RESTROOM EXHAUST OK TO COVER, EXCEPT TIRE CENTER |
|
02/08/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/07/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. AN-2 CHICKEN PREP AREA ROUGH DUCT OK TO INSULATE. 2. ROUND DUCT AT PHARMACY OK TO INSULATE PROVIDE BRANCH TAPS PER PLANS. 3. ROUND DUCT AT OFFICE AREA OK TO INSULATE. 4. ROUND DUCT AT OPTICAL OK TO INSULATE. |
|
02/03/2011 | MECHANICAL - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
01/25/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) DUCT ABOVE MEAT PREP OK TO COVER |
|
01/21/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE CONICAL TAPS PER PLANS/DETAILS 2) PROVIDE 45 DEGREE CONVERGING BRANCH TAPS ON RECTANGULAR DUCT PER PLANS/DETAILS 3) PROVIDE RADIUS THROATS ON RECTANGULAR ELBOWS PER PLANS/SPECS 4) PROVIDE WRITTEN APPROVAL FROM ENGINEER ON ALL CHANGES TO PLANS |