Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09CM03304

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/29/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
04/25/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
04/13/2011 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) LOADING DOCK RESTROOM AREA OK, PHARMACY OK, DEMO PREP OK, MENS & WOMENS PUBLIC RESTROOMS OK AND FOOD SERVICE OK
2) SUPPORT INDIRECT DRAINS AT SODA FOUNTAIN
3) COMPLETE WATER PIPING TO EXISTING SYSTEM TO ENSURE BACKFLOW IF REQUIRED IN TIRE CENTER AND INSTALL HOSE BIB OVERHEAD
4) TIRE CENTER OK
5) PROVIDE BACKFLOW PROTECTION FOR WATER TO DEVELOPER ? RECOVERY AND COMPLETE INSULATION BEHIND ACCESS PANEL FOR PHOTO AREA
6) OPITCAL AREA OK, BAKERY OK, MEAT PREP OK, ROTISSERIE OK AND DELI OK
7) NEED TO SEE EXTERIOR TRAFFIC RATED CLEANOUTS
04/11/2011 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
04/08/2011 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
04/07/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) BAKERY AREA ONLY-NO VACUUM BREAKER ON VALVE DOWN STREAM OF VACUUM BREAKER FOR WATER TO CHEMICAL ADDITION AT 4 COMP SINK
2) ALL CLEANOUTS PLUGS TO BE FACTORY TAPPED WITH MACHINE SCREWS
3) SUPPORT OVER HEAD PIPING AND SECURE
4) PROVIDE BACKFLOW PROTECTION FOR HOSE REEL AT WASHING SYSTEM
5) PROVIDE BACKFLOW PROTECTION FOR E-7 BAKERY OVENS PER P-3.1
6) PROVIDE DRAINS
7) PROVIDE LABELING RPPB
03/15/2011 PLUMBING - FINAL Not ready for Inspection 1. ONE SINGLE RESTROOM AT LOADING DOCK INSTALLED. CHLORINE INJECTION IN PROGRESS.