Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T09CM03304

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2011 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
03/25/2011 PLUMBING - GAS PRESSURE TEST Denied TEST NOT HOLDING, PROVIDE CORRECT FLEX FOR TIRE SHOP HEATER, TERMINATE ALL REGULATOR VENTS, ELECTRONIC SELONOID VALVE AT PIZZA OVENS NEED TO SEE LISTING, SUPPORT ALL PIPING, PIPE T&P FOR JANITOR ROOM WATER HEATER
03/22/2011 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) 60 PSI TEST ON ALL PIPING FROM EXTERIOR THRU TO REGUALTOR SHUT OFFS OK
2) NEED LOW PRESSURE TEST WITH COMPLETION OF REGULATOR VENTS THRU ROOF, INSTALL SESMIC VALVE ON EXTERIOR AND SUPPORT ALL GAS PIPING PER PLAN & CODE REQUIREMENTS
03/21/2011 PLUMBING - GAS PRESSURE TEST Denied 1. 60 PSI TEST NOT HOLDING. NOTE: PLEASE PROVIDE A LISTING FOR THE A/C VALVE SHOWN ON P2.4 BEING USED ON MEDIUM PRESSURE GAS SYSTEM.
03/07/2011 PLUMBING - GAS PRESSURE TEST Partial Approval 60 PSI TEST PER INITAL PAGE P.1 AT GANG BOX, COMPLETE 60 PSI TESTING TO ALL REGULATOR SHUT OFF VALVES.
03/02/2011 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) GAS DROPS FOR ROTISSERIE IN WALL ONLY TEST
2) DWV MEAT PREP IN WALL ONLY OK
3) (2) RD + (1) ? AT LOADING DOCK WATER TEST OK
4) SUPPORT PER REQUIREMENTS AND PROVIDE OVERFLOW DAMS ON OVER FLOW RAIN DRAINS ON ROOF
5) WATER IN WALL ONLY MEAT PREP ROTISSERIE, DELI AND DISH PREP
6) WATER IN WALL AND OVER HEAD TEST OK
7) COMPLETE SUPPORTS
8) DWV ROTISSERIE AND EAST TO DISH PREP TEST TO 5' FROM ROOF
03/01/2011 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
02/25/2011 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*