Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM03304

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/01/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1) ROTESSIERIE NOT COMPLTE (CHICKEN DISPLAY)
2) MEAT PREP-NEED TO PLUG UNUSED OPENINGS IN J-BOXES, SEAL PENETRATIONS
3) TIE WIRING UP AND AWAY FROM DOORS/FLOOR IPC'S IN MEZZ
4) ROLL UP DOES NOT COMPLETE HOOK UP
5) OK BAKERY
6) TIRE SHOP NOT READY (FANS)
7) OK ROOF
8) POLE BASE J-BOXES
03/25/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK PHARMACY COMPLETE
2) OK PHOTO, EYE EXAM AND PANEL P8
3) INSTALL BOND BUSHING AT FLEX TERMINATIONS ON AC UNITS
4) EXHAUST FANS NEEE RACEWAY FOR EXPOSED CONDUCTORS
03/17/2011 ELECTRIC - INTERMEDIATE Partial Approval ALL ELECTRIC ASSOCIATED WITH REFRIGERATION BOXES IS COMPLETE. CHECKED DISCONNECTS, J-BOXES, AND PANELS FOR ALL EXCEPT THE POS COOLERS.
03/15/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
KITCHEN:
1) PLEASE VERIFY LISTING FOR CONTACTOR IN HOOD MAKE UP BOX
2) SUPPORT M/C 12" 330.30
3) CLEAN DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL
4) CAP UNUSED CONDUIT OPENINGS ABOVE PANELS
5) 366.23 AND 366.22 APPLYS TO GUTTERS
03/11/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) P-4 LOCK NUT REVERSED
2) CHECKED EM EGRESS LTG OK
3) PANEL MAKE UP SALES FLOORS NOT COMPLETE YET
4) BAKERY ABOVE CEILING NOT READY
5) OK TO TCO FOR STOCKING AND RACKS
6) OK MILL WORK PHOTO AND OPTICAL
03/09/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) USE LISTED CONNECTORS FOR SO CORD. PHOTO AREA AND MEAT PACKING AREA
2) IN OPTICS, BOX EXTENSION
3) OK FEEDERS AT REFRIG. MEZZ AND SES
4) ADDRESS DERATING IN WIRE WAYS, OVER 30 CONDUCTORS
03/07/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FUSES IN SES COMPARTMENTS
2) BUSHINGS H2-FEEDERS/T-G #2 GROUND TO CW
3) NEED TO ADDRESS VFD CLEARANCE BY ROOF LADDER ON MEZZ.
4) OK WALK IN (POS.) ON FLOOR, RACKS A,B,C,D AND M5 COND. ON ROOF. PARTIAL MAKE UP IN H3 AND CONTACTOR FOR POS'S.
03/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ABOVE CEILING OFFICES AND PHARMACY
2) OK ISLAND CASES, FEEDS TO COMPRESSORS, NEED TO SEE TERMINATIONS/FEEDER MAKE UP IN ZPC'S
02/23/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS AND TIRE SHOP
02/16/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/15/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NEED COPY OF GFI MAIN TEST
2) OK WALLS OPTICAL, PHOTO AND SODA FOUNTAIN WALL
02/14/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) BONDING ON SUPPLY SIDE OF SES PER 250.92/250.66 (BOND BUSHING)
2) LOCK NUTS ON BOTH SIDES OF CHASE NIPPLES-OK BLDG STEEL LETTER OF TORQUE AND WATER BOND
3) NEED GFI MAIN TEST AND GEN TEST
02/11/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS BAKERY, FOOD SERVICE, OPTICAL, PHARMACY RESTROOM WALLS AND HARD LIDS
2) OK LIGHT FIXTURE MAKE UP IN COOLERS MEAT DEPT AND DELI
02/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/07/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
EMPLOYEE LOCKER ROOM, EXCEPT WEST WALL.
02/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK 1ST FLOOR OFFICES - WALLS
- 2ND FLOOR NOT COMPLETE
02/03/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
EMPLOYEE LOCKER ROOM, EXCEPT WEST WALL
02/01/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ROUGH MEN AND WOMEN RESTROOMS
01/28/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK ROUGH DEMO ROOM, PHARMACY, HEARING AND WALLS ONLY
01/26/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT EMT WITHIN 3' PER CODE
2) TIGHTEN FITTINGS THRU-OUT
01/24/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ok conduits in masonry chase under electrical room
01/21/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/20/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK POLE BASES
2) BE ADVISED TO USE BUSHINGS OR BELLS AT CONDUIT STUBS INTO PULL BOXES FOR SITE LTG, SPLICES RATED FOR WET LOCATION, BOND METAL COVERS IF APPLICABLE,
3) OK CONDUIT STUBS THRU ELECTRIC MEZZ FLOOR
01/10/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/04/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/27/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/17/2010 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/17/2010 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*