Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM03304
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1) ROTESSIERIE NOT COMPLTE (CHICKEN DISPLAY) 2) MEAT PREP-NEED TO PLUG UNUSED OPENINGS IN J-BOXES, SEAL PENETRATIONS 3) TIE WIRING UP AND AWAY FROM DOORS/FLOOR IPC'S IN MEZZ 4) ROLL UP DOES NOT COMPLETE HOOK UP 5) OK BAKERY 6) TIRE SHOP NOT READY (FANS) 7) OK ROOF 8) POLE BASE J-BOXES |
|
03/25/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PHARMACY COMPLETE 2) OK PHOTO, EYE EXAM AND PANEL P8 3) INSTALL BOND BUSHING AT FLEX TERMINATIONS ON AC UNITS 4) EXHAUST FANS NEEE RACEWAY FOR EXPOSED CONDUCTORS |
|
03/17/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | ALL ELECTRIC ASSOCIATED WITH REFRIGERATION BOXES IS COMPLETE. CHECKED DISCONNECTS, J-BOXES, AND PANELS FOR ALL EXCEPT THE POS COOLERS. | |
03/15/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* KITCHEN: 1) PLEASE VERIFY LISTING FOR CONTACTOR IN HOOD MAKE UP BOX 2) SUPPORT M/C 12" 330.30 3) CLEAN DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL 4) CAP UNUSED CONDUIT OPENINGS ABOVE PANELS 5) 366.23 AND 366.22 APPLYS TO GUTTERS |
|
03/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) P-4 LOCK NUT REVERSED 2) CHECKED EM EGRESS LTG OK 3) PANEL MAKE UP SALES FLOORS NOT COMPLETE YET 4) BAKERY ABOVE CEILING NOT READY 5) OK TO TCO FOR STOCKING AND RACKS 6) OK MILL WORK PHOTO AND OPTICAL |
|
03/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) USE LISTED CONNECTORS FOR SO CORD. PHOTO AREA AND MEAT PACKING AREA 2) IN OPTICS, BOX EXTENSION 3) OK FEEDERS AT REFRIG. MEZZ AND SES 4) ADDRESS DERATING IN WIRE WAYS, OVER 30 CONDUCTORS |
|
03/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FUSES IN SES COMPARTMENTS 2) BUSHINGS H2-FEEDERS/T-G #2 GROUND TO CW 3) NEED TO ADDRESS VFD CLEARANCE BY ROOF LADDER ON MEZZ. 4) OK WALK IN (POS.) ON FLOOR, RACKS A,B,C,D AND M5 COND. ON ROOF. PARTIAL MAKE UP IN H3 AND CONTACTOR FOR POS'S. |
|
03/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILING OFFICES AND PHARMACY 2) OK ISLAND CASES, FEEDS TO COMPRESSORS, NEED TO SEE TERMINATIONS/FEEDER MAKE UP IN ZPC'S |
|
02/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS AND TIRE SHOP |
|
02/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/15/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NEED COPY OF GFI MAIN TEST 2) OK WALLS OPTICAL, PHOTO AND SODA FOUNTAIN WALL |
|
02/14/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BONDING ON SUPPLY SIDE OF SES PER 250.92/250.66 (BOND BUSHING) 2) LOCK NUTS ON BOTH SIDES OF CHASE NIPPLES-OK BLDG STEEL LETTER OF TORQUE AND WATER BOND 3) NEED GFI MAIN TEST AND GEN TEST |
|
02/11/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS BAKERY, FOOD SERVICE, OPTICAL, PHARMACY RESTROOM WALLS AND HARD LIDS 2) OK LIGHT FIXTURE MAKE UP IN COOLERS MEAT DEPT AND DELI |
|
02/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
02/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* EMPLOYEE LOCKER ROOM, EXCEPT WEST WALL. |
|
02/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK 1ST FLOOR OFFICES - WALLS - 2ND FLOOR NOT COMPLETE |
|
02/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* EMPLOYEE LOCKER ROOM, EXCEPT WEST WALL |
|
02/01/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ROUGH MEN AND WOMEN RESTROOMS |
|
01/28/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK ROUGH DEMO ROOM, PHARMACY, HEARING AND WALLS ONLY |
|
01/26/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT EMT WITHIN 3' PER CODE 2) TIGHTEN FITTINGS THRU-OUT |
|
01/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ok conduits in masonry chase under electrical room |
|
01/21/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
01/20/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK POLE BASES 2) BE ADVISED TO USE BUSHINGS OR BELLS AT CONDUIT STUBS INTO PULL BOXES FOR SITE LTG, SPLICES RATED FOR WET LOCATION, BOND METAL COVERS IF APPLICABLE, 3) OK CONDUIT STUBS THRU ELECTRIC MEZZ FLOOR |
|
01/10/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/27/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/17/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
12/17/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |