Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2011 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 12/17/2010 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* | |
| 12/17/2010 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* 1) OK CADWELDS TO UFER IN TRENCH |
|
| 12/14/2010 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* 1) NEED GROUNDING ELECTRODE SYSTEM 2) FILL UNUSED OPENINGS 3) MAIN BACK FED BREAKER TO HAVE MANUFACTURERS HOLDOWN 4) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING AND CLEAN SURFACE UNDER BAR 5) PROTECT CONDUCTORS AT FITTINGS 352.46 & 300.4 |
|
| 12/07/2010 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* 1) PRE CONSTRUCTION MEETING WITH CONTRACTOR AND SUB CONTRACTOR |