Permit: T09CM03284

Parcel: 14026704A


Addresses:

2036 E CALLE CORZA


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09CM03284

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/10/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/08/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) FOAM REFRIDGERANT PIPE INSULATION IS TO BE COATED FOR PROTECTION FROM UV WHEN INSTALLED ON EXTERIOR OF BLDG PER MANUFACTURES INSTALLATION INSTRUCTIONS
2) LOW VOLTAGE CONTROL WIRING TO BE PROTECTED BY CONDUIT OR SOME OTHER MEANS FROM DAMAGE
3) PER SECTION 403.2.1 I.E.C.C. SUPPLY AND RETURN DUCTS SHALL BE INSULATED TO A MIN. R-8