Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM03277
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/04/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK PANEL FILLERS AND SEPERATION |
|
03/03/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CLEAN EXCESS PAINT AND FOREIGN MATERIAL FROM DEVICE TERMINALS 110.12 AND BOTTOM OF PANEL 2) BOXES MORE THAN 1/4" 314.20 3) FILL UNUSED OPENINGS IN PANEL 4) SUPPORT M/C CABLE TO CEILING BOX 5) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL 6) WAITING ON CORRECT LIGHTS 7) LABEL OUTSIDE PANEL COVER |