Permit: T09CM03272

Parcel: 107111920


Addresses:

3008 N CASTRO AV


Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Permit Number - T09CM03272

Inspection Description - BUILDING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
11/23/2010 BUILDING - PROGRESS Approved IVRS - Inspection :*
1) RECEIVED CHECK #91-567/1221 FOR $75.00
11/16/2010 BUILDING - PROGRESS Not ready for Inspection IVRS - Inspection :*
1) PROVIDE MEANS OF DISCONNECT AT SERVICE
06/25/2010 BUILDING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOTES 1, 4, 7 & 8 FROM PREVIOUS
2) NEW BEDROOM WINDOW EGRESS BLOCKED BY EVAPORATIVE COOLER NOT SAFE EGRESS TO PUBLIC WAY
3) PROVIDE WORKING SMOKE ALARM-HALLWAY
3) WORK TO SERVICE EQUIPMENT, NOT TO CODE
4) PROVIDE ACCESS TO EQUIPMENT FOR INSPECTION
04/29/2010 BUILDING - PROGRESS Not ready for Inspection IVRS - Inspection :*
1) LIGHT FIXTURE IN FURNACE ROOM COVER PLATE, TO CLOSE TO CEILING
2) HAVE QUALIFIED ELECTRICIAN CLEAN UP WIRING IN LAUNDRY-SUB PANELS
3) NEED IRON PIPE NIPPLE AT FURNACE CABINET, FLEX NOT TO ENTER CABINET
4) REMOVE ALL TAPE FROM SINGLE TO DBL WALL FLUES 3 SCREWS TO JOIN B-TYPE TO SINGLE WALL
5) ALL THREE HOLE WALL RECEPTS TO BE ON A GROUNDED SYSTEM, OR REPLACE WITH 2 HOLE, OR GFCI
6) T & P LINE TO BE A GRAVITY DRAIN, NOT TO TRAP H20
7) BATHROOM GFCI REQUIRED
8) SERVICE EQUIPMENT, HAVE ELECTRICIAN CHECK OUT WIRING FUSING AND DISCONNECTING MEANS